Our website offers parametric search capabilities allowing our customers to search for parts through a number of filters, one of which is by National Stock Number, or NSN. A National Stock Number is an identifier applied to any item of supply that is repeatedly procured, stocked, stored, issued, and used throughout the federal supply system. ASAP Inventory has a broad selection of NSN parts NE231050 such as 5925001590444 from manufacturers like Westinghouse Electric Corp. To begin the purchasing process immediately, submit an RFQ today.
MRC | Criteria | Characteristic |
---|---|---|
ABHP | OVERALL LENGTH | 6.000 INCHES NOMINAL |
ADTV | CASE MATERIAL | PLASTIC |
AEBV | UNTHREADED MOUNTING HOLE DIAMETER | 0.188 INCHES NOMINAL |
APNQ | ARC QUENCHING METHOD | DEION |
AXHR | MOUNTING FACILITY TYPE AND QUANTITY | 6 UNTHREADED HOLE |
CPRG | MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 5000.0 AC ALL LOCATIONS AND 5000.0 DC ALL LOCATIONS |
CPRJ | TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |
CPRL | TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
CPRQ | RESET METHOD | MANUAL |
CPRT | MANUAL ACTUATOR TYPE AND QUANTITY | 1 TOGGLE |
CQWN | TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 210.000 MINIMUM AT 125 PCT ALL LOCATIONS AND 4200.000 MAXIMUM AT 125 PCT ALL LOCATIONS AND 20.000 MINIMUM AT 200 PCT ALL LOCATIONS AND 105.000 MAXIMUM AT 200 PCT ALL LOCATIONS AND 8.000 MINIMUM AT 300 PCT ALL LOCATIONS AND 23.000 MAXIMUM AT |
FEAT | SPECIAL FEATURES | MTG HOLES IN 2 ROWS OF 3,1.375 BY 4.844 IN. C TO C |
TTQY | TERMINAL TYPE AND QUANTITY | 6 SCREW |
ABKW | OVERALL HEIGHT | 3.969 INCHES NOMINAL |
ABMK | OVERALL WIDTH | 4.125 INCHES NOMINAL |
AKPX | POLE QUANTITY | 3 |
CPLM | MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 15.0 AMPERES AC ALL LOCATIONS AND 15.0 AMPERES DC ALL LOCATIONS |
CPRF | OPERATING VOLTAGE TYPE AND RATING PER POLE IN VOLTS | 250.0 AC ALL LOCATIONS AND 125.0 DC ALL LOCATIONS |
CPRH | CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
CPRN | ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 125.0 ALL LOCATIONS |
CPRP | ULTIMATE TRIP TIME PER POLE IN SECONDS | 210.000 MINIMUM ALL LOCATIONS AND 4200.000 MAXIMUM ALL LOCATIONS |
CPRR | MAIN CONTACT TRIPPING MECHANISM TYPE | TRIP FREE |
CPRW | ACTUATOR FUNCTION | TRIP W/SEPARATE RESET |
CRCF | TRIP RELEASE AMBIENT TEMP RATING | 25.0 DEG CELSIUS NOMINAL ALL LOCATIONS |